Battery Sizing Calculator

Work out how much battery you need for each job, check the bank can deliver your biggest load, and get the inverter settings for the bank you choose. Companion tool to Chapter 5 of The Practical Solar Guide: Choosing a Battery.

Start with the number the Energy tab suggests, then adjust.
If you plan to expand later. Cables and the fused isolator should suit the final bank.

Checks

Settings and protection

Every battery casing and rack must be earthed. Ask your installer to show you the earth connection on each one (Chapter 5, section 5.8).

Battery module

Copy these from your battery datasheet.

If only depth of discharge is given: nominal kWh × DoD (e.g. 4.8 × 0.95 = 4.56).
Often given as a C-rate: 0.5C on a 100 Ah module = 50 A.
Check the exact model; this varies widely between brands (Chapter 5, section 5.4).

Inverter

High-voltage inverters often give this in kW instead: divide kW × 1000 by the battery voltage.
0.95 is a sensible allowance.

Job 1: Backup for outages (essential loads)

Fridges cycle on and off: use the average power, not the label rating. Hours: how long your typical outage lasts, or one night.

Job 2 and Job 3

From your Load Audit, or the "after" figure from your Efficiency Savings Estimator.
Typically 2 to 3 days.

Summary

Usable capacity needed = energy needed ÷ inverter efficiency. Modules = usable capacity needed ÷ usable capacity per module, rounded up.

Can the batteries deliver your biggest load?

e.g. kettle + microwave + lights. Use the Loads tab of the Inverter Sizing Calculator.

What each number of modules can supply

Charge acceptance: how much surplus solar the bank can absorb at its recommended rate. Above this, surplus is exported or wasted. Power is capped by the inverter's maximum battery current.